DS40VG Type 2 +3 AC surge protector, using CITEL's 'VG technology', to completely eliminate the leakAge and operation current while providing maximum discharge capacity and an optimized level of protection. The electric scheme includes a disconnector and its associated indicator. The DS40VG surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+N AC networks.
- Type 2 + 3 AC Multipolar surge protector
- In : 20 kA
- Imax total: 160 kA
- Pluggable module
- Follow and operating current : none
- No ageing
- Optional remote signaling state
- Optimized to TOV
- EN 61643-11, IEC 61643-11, UL1449 ed.4 compliance
|
SPD type
|
2+3 | |
|
Network
|
230/400 V 3-phase+N | |
|
AC system
|
TNS | |
|
Nominal line voltage
|
Un | 230 Vac |
|
Max. AC operating voltage
|
Uc | 255 Vac |
|
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
Without disconnection
|
UT | 335 Vac withstand |
|
Temporary Over Voltage (TOV) Charasteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 440 Vac withstand |
|
Residual Current
Leakage current to Ground
|
Ipe | None |
|
Operating current
Continious current at Uc
|
Ic | None |
|
Follow current
|
If | None |
|
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 40 kA |
|
Total Maximum discharge current
max. total withstand @ 8/20 µs
|
Imax Total | 160 kA |
|
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
|
Uoc | 6 kV |
|
Withstand on overvoltages IEEE C62.41.1
|
20 kV | |
|
Connection mode(s)
|
L/PE and N/PE | |
|
Protection mode(s)
|
Common mode/Differential mode | |
|
Residual voltage
@ In (8/20 µs)
|
Up-in | 0.8 kV |
|
Protection level L/PE
@ In (8/20µs)
|
Up L/PE | 1.25 kV |
|
Admissible short-circuit current
|
Isccr | 25 000 A |