DS50PV/51 are type 2 surge protectors are designed to protect against lightning surge voltages in photovoltaic power supply network. Based on the use of specific varistors, providing a protection in common mode or common and differential mode.
- Type 2 surge protector for Photovoltaic
- PV Voltage: 500 Vdc
- In : 15 kA
- Imax : 40 kA
- Pluggable module
- Remote signaling (option)
- IEC 61643-31/EN61643-31 compliance
SPD type
|
2 | |
Network
|
PV network 1250 Vdc | |
Nominal PV voltage
|
Uocstc | 500 Vdc |
Max. PV operating voltage
|
Ucpv | 530 Vdc |
Residual Current
Leakage current to Ground
|
Ipe | None |
PV Permanent Operating current
Current consumption at Ucpv
|
Icpv | < 0.1 mA |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 40 kA |
Total Maximum discharge current
max. total withstand @ 8/20 µs
|
Imax Total | 60 kA |
Current withstand short circuit PV
|
Iscpv | 15 000 A |
Connection mode(s)
|
+/-/PE | |
Protection mode(s)
|
Common/Differential mode | |
Protection level +/-
@ In (8/20µs)
|
Up | 6.8 kV |
Protection level +/PE (-/PE)
@ In (8/20µs)
|
Up | 1.5 kV |
Parameters
Rated voltage | 500V |
---|---|
Maximum operating voltage | 530V |
Download