The DS50VGPVS-G / 51 series is available for PV systems with voltages of 600V, 1000V and 1500Vdc. They comply with the French UTE Directive C61-740-51 and the European standard EN50539-11 and can be used in accordance with the new French UTE Directive C15-712-1 and the European standard EN50539-12. DS50VGPVS-G / 51 is a type 2 surge protector and is designed for DIN rail mounting. The plug-in protection module ensures quick replacement in the event of a fault.
The protection circuit with VG technology consists of a Y circuit with spark gaps filled with gas and powerful varistors. Because there are no operating and leakage currents, passive aging is prevented. The DS50VGPVS comes standard with remote signaling.
- Type 2 surge protector for photovoltaic
- VG technology
- 1500 Vdc
- No leakAge, no operating currents
- Improved life expectancy
- In/Imax : 15 / 40 kA
- Common/Differential mode protection
- Remote signaling (option)
- UTE C61-740-51, EN 50539-11 compliance
SPD type
|
2 | |
Network
|
PV network 1000 Vdc | |
Nominal PV voltage
|
Uocstc | 1000 Vdc |
Max. PV operating voltage
|
Ucpv | 1200 Vdc |
Residual Current
Leakage current to Ground
|
Ipe | None |
PV Permanent Operating current
Current consumption at Ucpv
|
Icpv | None |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 15 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 40 kA |
Total Maximum discharge current
max. total withstand @ 8/20 µs
|
Imax Total | 60 kA |
Current withstand short circuit PV
|
Iscpv | 1000 A |
Connection mode(s)
|
+/-/PE | |
Protection mode(s)
|
Common/Differential mode | |
Protection level +/-
@ In (8/20µs)
|
Up | 5.1 kV |
Protection level +/PE (-/PE)
@ In (8/20µs)
|
Up | 2.8 kV |
Rated voltage | 1000V |
---|---|
Maximum operating voltage | 1200V |